3.9
UNIVERSAL ACCESS TOILET
USE OF SPACE
CAPACITY
The Area for Use by All as Toilet and Change Facilities
One Minimum
DESCRIPTION OF SPACE
A space dedicated for use by anyone including young children.
To provide a fully enclosed area for provision of universally accessible toilet facilities in accordance
with AS1428 as well as change facilities for all ages including young children.
CONNECTED SPACES
Directly Connected to:
Spectator Seating | Kiosk | Canteen Queuing Area
Indirectly Connected to:
Sports Field
DIMENSIONS OF SPACE
Nominal Area
Nominal Length
Nominal Width
Min Ceiling | Soffit Height
6 m2
2,000 mm
3,000 mm
2,600 mm
REFERENCE DOCUMENTS THAT APPLY
Australian Standards
AS1428 Design for Access and Mobility
MATERIALS
LOCATION
Floor
Material
Finish
Concrete Slab
R10
with Floor Tile
Colour
Dimension
NOTE
White Colours are
not suitable
Fall to Floor Waste
Skirting
Wall
Cove Floor
Match Floor
Finish to Wall
Finish
9 mm Fibre
Gloss
Cement Sheet
with Wall Tile
150 mm
White Colours are
High
not suitable
Wall Tile Full Height
of Wall and to its
Full Extent
Epoxy Grout Not
Required
CAMDEN PUBLIC BUILDING DESIGN MANUAL
PAGE 213